The SV40KM2P4B SmartOnline® SV Series 40kVA 3-Phase On-Line Double-Conversion UPS System delivers true scalability and offers the highest level of secure, uninterrupted power protection. Featuring a modular, scalable design with high-efficiency voltage and frequency independent (VFI) operation, this on-line UPS system is ideal for protecting a variety of critical IT systems.
The SV40KM2P4B includes pre-installed input, bypass and output breakers, as well as a static transfer switch (STS), two 20kVA SV20PM power modules and four SVBM battery modules. Space is included for up to two additional user-installable SV20PM power modules. External ±120VDC battery options, such as BP240V370, are also available from Tripp Lite for even more extended runtime.
The Java-free HTML5-based WEBCARDLX interface enables full remote access for site power and UPS status monitoring, configuration, control and email notifications via secure web browser, SNMP, telnet or SSH. It supports 10/100 Mbps auto-sensing for optimum communication with an Ethernet network.
With up to 92% efficiency in standard mode and up to 99% efficiency in optional economy mode, this 40kVA UPS system helps you reduce operating and cooling costs. Automatic and manual bypass options keep connected equipment operational during routine maintenance or critical power module failure. Front-panel display offers full UPS condition and status reporting.
40kVA 36kW 3-Phase Medium-Chassis UPS System
- Supports 208/120V or 220/127V AC 50/60Hz Wye 4-wire plus Earth hardwire input and output wiring
- Dual hardwire input design enables operation from up to 2 power sources
- Network-grade sine-wave AC output with 1% output voltage regulation and less than 1% output total harmonic distortion
- Tested to UL 1778 (U.S.), CSA (Canada) and NOM (Mexico) standards
- High 0.9 power factor for maximum power to the connected load
Pre-Installed WEBCARDLX Network Interface
- Allows full remote access for power monitoring, configuration, control and email notifications via secure web browser, SNMP, telnet or SSH
- Supports 10/100 Mbps auto-sensing for communication with an Ethernet network
- Optional EnviroSense2 sensors (sold separately) enable site monitoring of temperature, humidity and contact-closure status
- No Java required
Modular, Scalable Design for Maximum Flexibility
- Modular configuration with hot-swappable power modules and batteries enables easy, fast maintenance with zero downtime
- Open slots for up to 2 additional 20kVA SV20PM power modules accommodate increased capacity up to 80kVA (or 60kVA with N+1 fault tolerance)
- Supports external ±120VDC battery options for even more extended runtime
Optional Economy Mode
- Up to 99% efficient in optional economy mode to lower operating and cooling costs
Wide Input/Narrow Output Voltage Operating Range
- Enables full continuous online operation during brownouts as low as 121V and overvoltages up to 253V
- Regulates output voltage within 1% of the selected nominal output voltage in on-line double-conversion mode
Advanced IGBT Inverter with Digital Signal Processor (DSP) Technology
- Provides for less than 2% input total harmonic distortion (THDi) to support 1:1 generator sizing and prevent the need to oversize generator systems relative to UPS capacity
Automatic and Manual Bypass Options
- Keep connected equipment operational during routine maintenance or critical power module failure
Products specifications
Attribute name | Attribute value |
---|
Package volume | 883000 cm³ |
Height | 8.54" |
Weight | 604.7 lbs |
Input current Total Harmonic Distortion (THD) | Y |
Input power factor | Double-conversion (Online) |
Number of input phases | 85078000 |
Number of output phases | 3 |
Width | 4.21" |
Depth | 30.2" |
Master (outer) case width | 11.6" |
Master (outer) case height | 9.84" |
Country of Origin | China |
Housing Material | Steel |
Input Frequency | 40 - 70 Hz |
Display Type | LCD |
Power factor | 0.9 |
UPS topology | Double-conversion (Online) |
Master (outer) case weight | 76.9 lbs |
Master (outer) case length | 34.3" |
Output voltage regulation | 1 % |
Crest factor | 3:1 |
Emergency Power Off (EPO) | Yes |
Serial interface | Yes |
EMI/RFI noise filtering | Yes |
Cold start | Yes |
Emergency Power Off (EPO) connector | Yes |
Compliance certificates | RoHS |
Form factor | Tower |
Product color | Black |
Sustainability certificates | RoHS |
Serial interface type | RS-232 |
Output power | 36000 W |
Noise level | 73 dB |
Surge energy rating | 2496 J |
Input operation voltage (max) | 50/60 Hz |
Output operation voltage (max) | 91 % |
Output voltage Total Harmonic Distortion (THD) | Sine |
Audible alarm modes | Alarm when on battery, Fault, Low battery alarm |
Output operation voltage (min) | 120 V |
Efficiency | 92 % |
Cooling type | Active |
Input operation voltage (min) | 120 V |
Waveform | Sine |
LED indicators | Yes |
Audible alarm(s) | Yes |
Surge protection | Yes |
Package height | 85.6" |
Package weight | 739.7 lbs |
Package depth | 34.3" |
Package width | 11.6" |
Quantity per master (outer) case | 1 pc(s) |
Manual | Yes |
Power plug | 50/60 Hz |
AC outlet types | Terminal |
Maximum current | 120 A |
Output power capacity | 40 kVA |
Operating altitude | Tower |
Storage temperature (T-T) | -15 - 60 °C |
Operating temperature (T-T) | 0 - 40 °C |
Operating relative humidity (H-H) | 0 - 95 % |
Typical backup time at full load | 10 min |
Typical backup time at half load | 22 min |
Hot-swap battery | Yes |